Portal›Maintenance Plan
Maintenance Plan Engineering
Converts approved task logic into scheduling / trigger rules and lean SAP execution. Not every maintenance activity requires a cyclic work order.
Registered Plans - Assets
36.036
16.0% coverage
Plan Engineering Rows
314
One per maintenance task
SAP Plan Patterns
8
PA-01 through PA-08 plan patterns
Actual Call-Detail Assets
19.574
Matched from RU Sheet2
SAP Plan Patterns
| Code | Plan Pattern | Use Case | Call Object | Routine Plan? | Default Grouping | Task Rows |
|---|---|---|---|---|---|---|
| PA-01 | Monitoring / No Routine SAP Plan | Continuous/online monitoring; exception-driven action | None | No | System/area monitoring route | 37 |
| PA-02 | Inspection / Routine Notification | Simple inspection / due-date / condition route | Notification | Yes | Route/circuit/area/due window | 120 |
| PA-03 | Test / Calibration Notification | Simple test/calibration/proving | Notification | Yes | Unit + discipline + method + due window | 12 |
| PA-04 | Campaign / Package WO | Repetitive work needing resources / permit / vendor | Package WO | Yes | Area/unit + discipline/vendor + common window | 76 |
| PA-05 | Individual Planned WO | Unique asset-specific scheduled work | Individual WO | Yes | Equipment-specific | 0 |
| PA-06 | TA / Shutdown Package | Intrusive work requiring outage/TA | Package WO | Conditional | TA/unit/system/work package | 14 |
| PA-07 | Condition-Triggered WO | Repair/restoration from finding/diagnostic | Individual WO | No routine cyclic plan | Finding/equipment/defect | 54 |
| PA-08 | RTF / Corrective | Approved failure-event workflow | Corrective Notification / WO | No preventive plan | Equipment/failure event | 1 |
Maintenance Plan Engineering Library - Task ID deep-links back to the Task List.314 rows
| Task ID | Family | Task Title | Final Frequency / Trigger Rule | Owner | Plan Pattern | SAP Plan Type | Call Object | Routine? |
|---|---|---|---|---|---|---|---|---|
| EL-PANEL-FT-01 | Electrical Panel / Distribution / Control Panel | Electrical Panel Functional / Protection Test | At approved test due date; use outage window if isolation/shutdown is required. | Reliability + Discipline | PA-04 CAMPAIGN / PACKAGE WO | Strategy / single-cycle / counter campaign plan | Package WO | Yes |
| EL-PANEL-OVH-01 | Electrical Panel / Distribution / Control Panel | Electrical Panel Condition-Triggered Repair / Overhaul | Condition trigger; execute in next suitable outage unless risk requires earlier action. | Reliability + Maintenance / OEM | PA-07 CONDITION-TRIGGERED WO | Event-triggered workflow; no routine cyclic plan | Individual WO | No |
| EL-AUX-INS-01 | Electrical Auxiliary: Cable / Earthing / Lighting / Cathodic Protection | Electrical Auxiliary System Visual / Physical Condition Inspection | Periodic baseline from OEM/site history/P-F interval; adverse condition triggers earlier action. | Inspection / Asset Integrity | PA-02 INSPECTION / ROUTINE NOTIFICATION | Due-date / single-cycle / strategy notification plan | Notification | Yes |
| EL-AUX-CM-01 | Electrical Auxiliary: Cable / Earthing / Lighting / Cathodic Protection | Electrical Auxiliary System Thermography / Electrical Condition Monitoring | Periodic baseline from OEM/site history/P-F interval; adverse condition triggers earlier action. | Reliability / Condition Monitoring | PA-02 INSPECTION / ROUTINE NOTIFICATION | Due-date / single-cycle / strategy notification plan | Notification | Yes |
| EL-AUX-PM-01 | Electrical Auxiliary: Cable / Earthing / Lighting / Cathodic Protection | Electrical Auxiliary System Detailed Preventive Maintenance / Cleaning / Torque Check | Per OEM requirement and planned outage window. | Reliability + Maintenance Discipline | PA-04 CAMPAIGN / PACKAGE WO | Strategy / single-cycle / counter campaign plan | Package WO | Yes |
| EL-AUX-FT-01 | Electrical Auxiliary: Cable / Earthing / Lighting / Cathodic Protection | Electrical Auxiliary System Functional / Protection Test | At approved test due date; use outage window if isolation/shutdown is required. | Reliability + Discipline | PA-04 CAMPAIGN / PACKAGE WO | Strategy / single-cycle / counter campaign plan | Package WO | Yes |
| EL-AUX-OVH-01 | Electrical Auxiliary: Cable / Earthing / Lighting / Cathodic Protection | Electrical Auxiliary System Condition-Triggered Repair / Overhaul | Condition trigger; execute in next suitable outage unless risk requires earlier action. | Reliability + Maintenance / OEM | PA-07 CONDITION-TRIGGERED WO | Event-triggered workflow; no routine cyclic plan | Individual WO | No |
| EL-TRANSFORMER-CM-02 | Transformer | Oil-Immersed Transformer Oil / DGA / Moisture Assessment | Per sampling programme; adverse condition can trigger earlier sampling/action. | Reliability / Condition Monitoring | PA-02 INSPECTION / ROUTINE NOTIFICATION | Due-date / single-cycle / strategy notification plan | Notification | Yes |
| EL-UPS-DC-FT-02 | UPS / DC Power / Battery Charger | UPS / Battery Autonomy or Capacity Test | Per OEM and condition history. | Reliability + Discipline | PA-04 CAMPAIGN / PACKAGE WO | Strategy / single-cycle / counter campaign plan | Package WO | Yes |
| EL-AUX-CAL-01 | Electrical Auxiliary: Cable / Earthing / Lighting / Cathodic Protection | Cathodic Protection Potential Measurement / Verification | Per cathodic-protection monitoring / inspection programme. | Instrument / Metrology | PA-02 INSPECTION / ROUTINE NOTIFICATION | Due-date / single-cycle / strategy notification plan | Notification | Yes |
| IN-FIELD-INST-INS-01 | Field Instrument / Transmitter / Sensor / Indicator | Field Instrument Visual / Installation Inspection | Use approved route interval based on P-F interval / history; no universal cycle. | Inspection / Asset Integrity | PA-02 INSPECTION / ROUTINE NOTIFICATION | Due-date / single-cycle / strategy notification plan | Notification | Yes |
| IN-FIELD-INST-CM-01 | Field Instrument / Transmitter / Sensor / Indicator | Field Instrument Diagnostic / Performance Surveillance | Continuous monitoring + periodic engineering review at approved site interval. | Reliability / Condition Monitoring | PA-01 MONITORING / NO ROUTINE SAP PLAN | No routine SAP plan | None | No |
| IN-FIELD-INST-FT-01 | Field Instrument / Transmitter / Sensor / Indicator | Field Instrument Functional / Loop / Performance Test | Per approved proof/functional-test interval; condition can trigger earlier. | Reliability + Discipline | PA-04 CAMPAIGN / PACKAGE WO | Strategy / single-cycle / counter campaign plan | Package WO | Yes |
| IN-FIELD-INST-CAL-01 | Field Instrument / Transmitter / Sensor / Indicator | Field Instrument Calibration / Metrological Verification | Per approved metrology / drift-history / criticality calibration interval. | Instrument / Metrology | PA-04 CAMPAIGN / PACKAGE WO | Strategy / single-cycle / counter campaign plan | Package WO | Yes |
| IN-FIELD-INST-OVH-01 | Field Instrument / Transmitter / Sensor / Indicator | Field Instrument Condition-Triggered Repair / Restoration | Condition/finding triggered; no routine calendar cycle. | Reliability + Maintenance / OEM | PA-07 CONDITION-TRIGGERED WO | Event-triggered workflow; no routine cyclic plan | Individual WO | No |
| IN-CONTROL-VALVE-INS-01 | Control Valve / Final Control Element | Control Valve Visual / Installation Inspection | Use approved route interval based on P-F interval / history; no universal cycle. | Inspection / Asset Integrity | PA-02 INSPECTION / ROUTINE NOTIFICATION | Due-date / single-cycle / strategy notification plan | Notification | Yes |
| IN-CONTROL-VALVE-CM-01 | Control Valve / Final Control Element | Control Valve Diagnostic / Performance Surveillance | Continuous monitoring + periodic engineering review at approved site interval. | Reliability / Condition Monitoring | PA-01 MONITORING / NO ROUTINE SAP PLAN | No routine SAP plan | None | No |
| IN-CONTROL-VALVE-FT-01 | Control Valve / Final Control Element | Control Valve Functional / Loop / Performance Test | Per approved proof/functional-test interval; condition can trigger earlier. | Reliability + Discipline | PA-04 CAMPAIGN / PACKAGE WO | Strategy / single-cycle / counter campaign plan | Package WO | Yes |
| IN-CONTROL-VALVE-CAL-01 | Control Valve / Final Control Element | Control Valve Calibration / Metrological Verification | Per approved metrology / drift-history / criticality calibration interval. | Instrument / Metrology | PA-04 CAMPAIGN / PACKAGE WO | Strategy / single-cycle / counter campaign plan | Package WO | Yes |
| IN-CONTROL-VALVE-OVH-01 | Control Valve / Final Control Element | Control Valve Condition-Triggered Repair / Restoration | Condition/finding triggered; no routine calendar cycle. | Reliability + Maintenance / OEM | PA-07 CONDITION-TRIGGERED WO | Event-triggered workflow; no routine cyclic plan | Individual WO | No |
| IN-ESD-FINAL-INS-01 | ESD Final Element / Solenoid / Shutoff Valve | ESD Final Element Visual / Installation Inspection | Use approved route interval based on P-F interval / history; no universal cycle. | Inspection / Asset Integrity | PA-02 INSPECTION / ROUTINE NOTIFICATION | Due-date / single-cycle / strategy notification plan | Notification | Yes |
| IN-ESD-FINAL-CM-01 | ESD Final Element / Solenoid / Shutoff Valve | ESD Final Element Diagnostic / Performance Surveillance | Continuous monitoring + periodic engineering review at approved site interval. | Reliability / Condition Monitoring | PA-01 MONITORING / NO ROUTINE SAP PLAN | No routine SAP plan | None | No |
| IN-ESD-FINAL-FT-01 | ESD Final Element / Solenoid / Shutoff Valve | ESD Final Element Functional / Loop / Performance Test | Per approved proof/functional-test interval; condition can trigger earlier. | Reliability + Discipline | PA-04 CAMPAIGN / PACKAGE WO | Strategy / single-cycle / counter campaign plan | Package WO | Yes |
| IN-ESD-FINAL-CAL-01 | ESD Final Element / Solenoid / Shutoff Valve | ESD Final Element Calibration / Metrological Verification | Per approved metrology / drift-history / criticality calibration interval. | Instrument / Metrology | PA-04 CAMPAIGN / PACKAGE WO | Strategy / single-cycle / counter campaign plan | Package WO | Yes |
| IN-ESD-FINAL-OVH-01 | ESD Final Element / Solenoid / Shutoff Valve | ESD Final Element Condition-Triggered Repair / Restoration | Condition/finding triggered; no routine calendar cycle. | Reliability + Maintenance / OEM | PA-07 CONDITION-TRIGGERED WO | Event-triggered workflow; no routine cyclic plan | Individual WO | No |